CLIMATEMASTER WATER-SOURCE HEAT PUMPS
W (ERV) Series
Rev.: 15 May, 2015
12
ClimateMaster Water-Source Heat Pumps
Mist Eliminator Filter in Intake Hood (3HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 N/A 900 1045 1135 1255 1395 1410
1600 880 1035 1130 1245 1385 1405
1450
2000 1045 1145 1235 1325 1400 1440 1555
2400 1135 1300 1375 1435 1505 1550 1590
2800 1295 1365 1435 1515 1580 1625 1695
Barometric Hood, 2" Pleated Filters (3HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 N/A 955 1075 1185 1285 1355
1495
1600 945 1055 1175 1265 1335 1445 1635
2000 1045 1170 1330 1395 1440 1570 1695
2400 1210 1325 1435 1510 1580 1620 1675
2800 1315 1475 1500 1595 1710 1755 1790
SUPPLY
EXHAUST
RPM Range
Low 950-1320 Standard Unit
Medium 1325-1565 Optional Kit
High 1570-1880 Optional Kit
Mist Eliminator Filter in Intake Hood (3HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
2000 735 860 920 1005 1075 1150
1220
2400 850 945 1030 1090 1110 1215 1265
2800 935 1020 1080 1145 1200 1255 1335
3200 1015 1075 1105 1195 1285 1325 1380
3600 1065 1125 1220 1305 N/A N/A N/A
Barometric Hood, 2" Pleated Filters (3HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
2000 740 855 930 970 1080
1155 1240
2400 800 925 1015 1075 1145 1225 1280
2800 885 1010 1070 1140 1235 1255 1330
3200 950 1065 1135 1230 1290 1325 N/A
3600 1055
1130 1235 1280 1310 N/A N/A
SUPPLY
EXHAUST
RPM Range
Low 700-1025 Standard Unit
Medium 1030-1305 Optional Kit
High 1325-1575 Optional Kit
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Blower RPM for WD
Blower RPM for WE