ClimateMaster NB Series Instrukcja Obsługi Strona 11

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 16
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 10
THE SMART SOLUTION FOR ENERGY EFFICIENCY
W (ERV) Series
Rev.: 15 May, 2015
11
climatemaster.com
Mist Eliminator Filter in Intake Hood (1.5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
300 N/A N/A 980 1065 1320 1400
1520
500 N/A 905 1050 1215 1360 1495 1595
700 865 1035 1210 1330 1440 1535 1620
900 1030 1205 1325 1435 1530 1615 1725
1100 1200 1320 1430 1525 1605 1720 1800
Barometric Hood, 2" Pleated Filters (1.5HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
300 N/A 815 1030 1185 1305
1450 1535
500 N/A 950 1075 1220 1375 1490 1610
700 810 1070 1195 1295 1445 1510 1645
900 995 1125 1290 1405 1500 1600 1690
1100 1120 1280 1400 1495 1595 1685 1770
SUPPLY
EXHAUST
Low 1000-1300 Standard Unit
Medium 1300-1750 Optional Kit
High 1750-2200 Optional Kit
RPM Range
Mist Eliminator Filter in Intake Hood (2HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 990 1075 1220 1380 1480
1605 1720
1400 1030 1165 1280 1410 1520 1620 1740
1600 1135 1250 1340 1445 1570 1665 1760
1800 1240 1330 1425 1550 1625 1720 1785
2000 1295 1405 1540 1615 1705 1760 1830
Barometric Hood, 2" Pleated Filters (2HP)
External Static Pressure (in water)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 900 1085 1235 1380 1495
1585 1680
1400 1050 1220 1345 1490 1535 1630 1715
1600 1205 1335 1430 1520 1625 1705 1790
1800 1315 1425 1510 1580 1655 1775 1850
2000 1390 1490 1570 1650 1735 1750 N/A
SUPPLY
EXHAUST
RPM Range
Low 1000-1300 Standard Unit
Medium 1300-1700 Optional Kit
High 1700-2080 Optional Kit
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Blower RPM for WB
Blower RPM for WC
Przeglądanie stron 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16

Komentarze do niniejszej Instrukcji

Brak uwag